7. Check configuration of Probe Type. The following Probe Types are available:
Rigid twin
Flexible twin
Coaxial, coaxial HP/C, coaxial HTHP
Coaxial large, Coaxial large HP/C
Rigid single, rigid single HTHP/HP/C, rigid single PTFE
Flexible single, flexible single HTHP/HP/C, flexible single PTFE
The transmitter automatically makes some initial calibrations based on the selected
Probe Type. Normally, the Probe Type is pre-configured at the factory.
8. Check the entered Probe Length. See Probe length for further information.
9. Select the TRANSDUCER1100 block, and then select the Geometry tab.
10. Enter the Tank Height. See Tank height for further information.
11. Select the Mounting Type.
12. If using pipe, chamber or nozzle, then select the Inner Diameter.