13. If using nozzle, then enter the Nozzle Height.
14. Select the Environment tab.
15. Select the Measurement Mode. See Measurement mode for further information.
16. Enter the Product Dielectric Range/Upper Product Dielectric. See Product
dielectric range and Upper product dielectric constant for further information.
17. Select the Rapid level changes check-box only if the surface is moving quickly up or
down at rates over 1.5 in./s (40 mm/s).
18. To configure volume calculation, select the TRANSDUCER1300 block, and then
select the Volume tab.
19. In the Volume Calc method list, select the Volume Calculation Method. Choose
from:
None (if volume calculation is not desired at all)
Use strapping table (if the actual tank does not match any of the available
options for pre-defined tanks, or if higher calculation accuracy is desired)
Sphere
Vertical cylinder
Reference Manual Configuration
00809-0100-4530 April 2019
Reference Manual 143