Table 7-17: Troubleshooting Chart (continued)
Symptom Possible cause Action
FOUNDATION Fieldbus Card to
Transmitter Communication
Fault
Verify Device Mode setting, should be
FOUNDATION Fieldbus (Parameter:
ENV_DEVICE_MODE)
Restart method from Resource Block
Reboot gauge (Cycle Power)
Level Measurement Failure Check Power Supply
Check the gauge configuration
(Transducer Block)
Check that the mechanical installation
is correct
Temperature Measurement
Failure
Check ambient temperature
(2)
Restart gauge
Contact Emerson Service Department
Volume Measurement Failure Restart gauge
Check gauge configuration using PC
Based configuration tool
No surface echo Check signal strength
Restart transmitter
See Example 1: Product surface peak
not found
DB Error/ Microwave Unit
Error/ Configuration Error/
Other Error
Restart transmitter
Set database to default; load default
Database
Download Application Software
Call Service Center
SW Error/ Display Error/
Analog Out Error
Restart transmitter
Call Service Center
(1) A malfunctioning display panel may only be replaced by service personnel at the Emerson service department. A display
must not be replaced when the transmitter is in operation.
(2) If the Rosemount 5300 Level Transmitter has been exposed to temperatures outside the specified limits, the device may
stop its normal operation.
Service and troubleshooting Reference Manual
April 2019 00809-0100-4530
186 Rosemount 5300 Level Transmitter