• When using remote housing, make sure it is fully assembled before calibrating the
Vapor Compensation function.
Procedure
1. Verify the basic configuration for device has been performed.
2. Make sure the correct probe type is selected.
a) HART
®
: Select Configure → Manual Setup → Level Setup.
FOUNDATION
™
Fieldbus: Select Configure → Manual Setup.
b) Select the Probe tab.
c) In the Probe type list, select Coaxial HTHP for probe type 3V or Rigid Single
HTHP 0.3″ (8mm) for probe type 4U.
d) Select Send.
3. Check that Mounting Type is set to Pipe/Chamber and select inner diameter.
a) HART: Select Configure → Manual Setup → Level Setup.
FOUNDATION Fieldbus: Select Configure → Manual Setup.
b) Select the Geometry tab.
c) In the Mounting Type list, select Pipe/Chamber.
d) In the Inner Diameter, Pipe/Chamber/Nozzle list, select the corresponding
inner diameter.
e) Select Send.
4. HART: Select Configure → Manual Setup → Level Setup.
FOUNDATION Fieldbus: Select Configure → Manual Setup → Advanced.
5. HART: Select the Vapor Compensation tab.
FOUNDATION Fieldbus: Select the Vapor Compensation Setup button.
6. In the Reference Reflector Type list, select reference reflector as appropriate, and
then select Next.
Option
Description
Coax, l=350 mm (RR B3 in old DD
versions)
Use this option for probe type 3V with
short reflector
Coax, l=500 mm (RR B4 in old DD
versions)
Use this option for probe type 3V with
long reflector
d=13 mm, l=350 mm (RR A6 in old
DD versions)
Use this option for probe type 4U with
short reflector
d=13 mm, l=500 mm (RR B2 in old DD
versions)
Use this option for probe type 4U with
long reflector
7. HART: Select the Use Vapor Compensation checkbox, and then select Send.
Advanced configuration Reference Manual
April 2019 00809-0100-4530
412 Rosemount 5300 Level Transmitter