Table I-3: RB.RECOMMENDED_ACTION (continued)
Alarm type Failed/Maint/Advise Active
event
Recommended action text
string
Advisory Non-Volatile Writes
Deferred
Non-volatile writes have
been deferred, leave the
device powered until the
advisory goes away.
Electronics Warning -
Transducer Block
Check device installation
and configuration
Alerts Simulation Use the switch on the
Fieldbus electronics board
to turn simulation on or off.
Maintenance Probe Contamination Clean the probe.
Configuration Error Load default database to the
device and reconfigure it.
Configuration Warning Check device configuration
Simulation Mode Use Start/Stop Device
Simulation to enable or
disable simulation.
Vapor Compensation
Warning
• Recalibrate vapor
compensation.
• Check Vapor DC
configuration.
• Check that the correct
probe is attached.
Alerts Maintenance (continued) Volume/Temperature
Measurement Warning
• Check volume
configuration.
• Check ambient
temperature at
installation site.
• If the surrounding
temperature is OK, it
might indicate a
hardware error
producing heat. Replace
the transmitter head.
Resource Transducer Block Reference Manual
April 2019 00809-0100-4530
454 Rosemount 5300 Level Transmitter