Figure J-5: Analog Input Function Block Diagram for a Typical Level Transmitter
$
%
(
&
'
A. Level measurement
B. AI function block
C. OUT_D
D. OUT
E. To another function block
J.9.2
Application example 2
Radar level gauge, level value in percent (%)
The maximum level in the tank is 46 ft. (14 m). The level value is displayed in percentage of
the full span (see Figure J-6).
Figure J-6: Situation Diagram
$
&
%
A. 100%
B. 46 ft. (14 m)
C. 0%
Solution
Table J-6 lists the appropriate configuration settings, and Figure J-7 illustrates the correct
function block configuration.
Reference Manual Analog-Input Block
00809-0100-4530 April 2019
Reference Manual 469