Verify possibility to shorten the large coaxial probe
The inner probe consists of one to three segements depending on probe length. The
connection part between two inner probe segements must not be cut. Before shortening
the large coaxial probe, verify that your desired probe length is permitted for cutting.
Check your ordered probe length and desired probe length in table Table 3-11 or Table
3-12, and follow the action instruction.
Figure 3-22: Ordered Probe Length (L) vs Desired Probe Length (X)
/;
Table 3-11: Check Desired Cutting Probe Length (mm)
Ordered probe length
(L)
Desired probe length
(X)
Action
300 ≤ L ≤2100
300 ≤ X < 2100 Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
2100 < L ≤ 4100
300 ≤ X < 1960 Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
1960 ≤ X ≤ 2055 A new inner probe segement must be ordered,
contact your local Emerson representative.
2055 < X < 4100 Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
4100 < L ≤ 6000
300 ≤ X < 1960 Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
1960 ≤ X ≤ 2055 A new inner probe segement must be ordered,
contact your local Emerson representative
2055 < X < 3860 Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
3860 ≤ X ≤ 3955 A new inner probe segement must be ordered,
contact your local Emerson representative
3955 < X < 6000
Cutting can be performed. Follow instruction,
Shorten the large coaxial probe.
Mechanical installation Reference Manual
April 2019 00809-0100-4530
52 Rosemount 5300 Level Transmitter