3.5.2 Tank connection with loose flange (plate design)
The transmitter is delivered with head, flange and probe assembled into one unit. If, for
some reason, these parts have been disassembled, mount the transmitter as described
below.
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Mount the flange on the probe and tighten the flange nut.
60 mm
2. Place a suitable gasket on top of the tank flange.
3. Lower the probe with flange into the tank.
4. Tighten bolts and nuts with sufficient torque for the flange and gasket choice.
Mechanical installation Reference Manual
April 2019 00809-0100-4530
70 Rosemount 5300 Level Transmitter