97
Reference Manual
00809-0100-4026, Rev HA
Section 5: Basic Configuration/Start-up
November 2014
Basic Configuration/Start-up
Measure and Learn function
12. Select the Yes button to run the Measure and
Learn function. If No is selected, this function
can be run at a later stage using the Spectrum
Analyzer in RRM.
Make sure there is no filling or emptying
occurring when the Measure and Learn function
is used.
Tank precondition settings
13. The Measure and Learn function creates an ATC
automatically and suggests False Echo Areas.
See “Echo tuning” on page 83.
(By selecting the Advanced button, one or both
of the options can be selected in the
corresponding check-box).
Verify the Tank Precondition settings. Verify that
the Distance to Surface value is correct. If not, it
may be due to a disturbing object in the tank).
Select Empty Tank if the tank is empty.
Spectrum plot
14. The automatically created ATC and False Echo
Areas are shown in the Spectrum Plot. False Echo
Areas are presented as shaded areas, and
represent tank levels where RRM found
interfering echoes to be blocked out. False Echo
Areas can be moved or removed before storing
to the transmitter database. Verify that each
False Echo Area is identified as an object in the
tank that gives rise to a disturbing echo. See
“Echo tuning” on page 83 for more information.
Select the Store button to save the ATC and the
registered disturbance echoes.