Section 5: Basic Configuration/Start-up
November 2014
Basic Configuration/Start-up
Analog output
9. Typically, the Primary Variable (PV) is
configured to be Product Level or Volume.
Set the analog output range by inputting the
Lower Range Value (4 mA) and the Upper
Range Value (20 mA) to the desired values.
The Alarm Mode specifies the output state
when a measurement error occurs.
HART command: [2, 1, 5].
See Analog output (HART)” on page 81 for
more information on Analog Output
configuration and Alarm Mode settings.
Finish Configuration Wizard
10. This is the last window in the Configuration
Wizard. The configuration can be changed at any
time by using the Setup windows (General, Tank,
Output etc., see “Using the Setup functions” on
page 100), which contain further options not
available in the configuration wizard.
Select the Finish button and continue with the
next step in the Guided Setup.
Echo tuning
11. Step 2 in the Guided Setup allows automatic
configuration of the ATC and registration of false
echoes by running the Measure and Learn
function. See “Echo tuning” on page 83 for more
information on amplitude thresholds and false
echoes.
Click button 2 to start the Measure and Learn
function.
(If Echo Tuning is not needed, or is done at a later
stage, go on to step 3 in the Guided Setup).