95
Reference Manual
00809-0100-4026, Rev HA
Section 5: Basic Configuration/Start-up
November 2014
Basic Configuration/Start-up
Tank Environment
7. In the Process Condition box, select the
check-boxes that correspond to the conditions
of the tank. Select as few options as possible and
no more than two. See Process conditions” on
page 77 for more information.
F
OUNDATION fieldbus parameter:
TRANSDUCER_1100 > ENV_ENVIRONMENT.
The Dielectric Chart lists the dielectric constants
of a large number of products and can be
opened by selecting View > Dielectric Constant
Chart menu option.
Select the Product Dielectric Range that
corresponds to the current product. If the
correct range value for this parameter is
unknown, or the contents in the tank are
continually changing, choose Unknown.
HART command: [2, 1, 3, 2].
F
OUNDATION fieldbus parameter:
TRANSDUCER_1100 > ENV_DIELECTR_CONST.
Volume
8. For volume calculation, select a pre-defined
calculation method based on a tank shape that
corresponds to the actual tank. Select None if
volume calculation is not needed.
The Strapping Table option is used if the actual
tank does not match any of the available options
for pre-defined tanks or if higher calculation
accuracy is desired.
HART command: [2, 1, 4, 1].
F
OUNDATION fieldbus parameters:
ADV_CONFIG_TB_1300 >
VOL_VOLUME_CALC_METHOD/
VOL_IDEAL_DIAMETER/
VOL_IDEAL_LENGTH/
VOL_VOLUME_OFFSET.
For more information, see “Volume
configuration” on page 78.