Resource Block
SIMULATE_STATE 66 0x01(Jumper off* no
simulation)
The state of the simulate switch:
0 = Uninitialized
1 = Switch off, simulation not allowed
2 = Switch on, simulation not allowed (need to cycle
jumper/switch)
3 = Switch on, simulation allowed
download_mode 67 0x01(Run Mode) Gives access to the boot block code for over-the-wire
downloads.
0 = Uninitialized
1 = Run mode
2 = Download mode
RECOMMENDED_ACTION 68 0x0001
(No action required.)
Enumerated list of recommended actions displayed
with a device alert.
FAILED_PRI 69 0 Designates the alarming priority of the FAILED_ALM.
FAILED_ENABLE 70 0x00007760
(Software Error | Sensor
Database Error | Internal
Temperature Critical |
Electronics Failure - Main
Board | Software
Incompatibility Error |
Memory Failure - Output
Board | Internal
Communication Failure
| Electronics Failure -
Output Board)
Enabled FAILED_ALM alarm conditions. Corresponds
bit for bit to the FAILED_ACTIVE. A bit on means that
the corresponding alarm condition is enabled and will
be detected. A bit off means the corresponding alarm
condition is disabled and will not be detected.
FAILED_MASK 71 0x00000000
(0x00000000)
Mask of FAILED_ALM. Corresponds bit of bit to
FAILED_ACTIVE. A bit on means that the condition is
masked out from alarming.
FAILED_ACTIVE 72 0x00000000
(0x00000000)
Enumerated list of failure conditions within a device.
FAILED_ALM 73 Alarm indicating a failure within a device which makes
the device non-operational.
MAINT_PRI 74 0 Designates the alarming priority of the MAINT_ALM
MAINT_ENABLE 75 0x08608000
(Device Simulation
Active | Configuration
Warning | Internal
Temperature Out of
Limits | Configuration
Error
Enabled MAINT_ALM alarm conditions. Corresponds
bit for bit to the MAINT_ACTIVE. A bit on means that
the corresponding alarm condition is enabled and will
be detected. A bit off means the corresponding alarm
condition is disabled and will not be detected.
MAINT_MASK 76 0x00000000
(0x00000000)
Mask of MAINT_ALM. Corresponds bit of bit to
MAINT_ACTIVE. A bit on means that the condition is
masked out from alarming.
MAINT_ACTIVE 77 0x00000000
(0x00000000)
Enumerated list of maintenance conditions within a
device.
MAINT_ALM 78 Alarm indicating the device needs maintenance soon.
If the condition is ignored, the device will eventually
fail.
ADVISE_PRI 79 0 Designates the alarming priority of the ADVISE_ALM
ADVISE_ENABLE 80 0x10000000
(PlantWeb
®
Alerts
Simulation Active)
Enabled ADVISE_ALM alarm conditions. Corresponds
bit for bit to the ADVISE_ACTIVE. A bit on means that
the corresponding alarm condition is enabled and will
be detected. A bit off means the corresponding alarm
condition is disabled and will not be detected.