Reference Manual
00809-0100-4731, Rev FA
April 2003
A-5
APEX
and APEX Sentry
Radar Gauge
ENVIRONMENTAL
CONDITIONS
APEX and APEX Sentry
Humidity: 5 to 100% relative humidity (with covers on and tightened to
achieve metal-to-metal contact)
Electronics/Housing temperature ranges:
Standard: –40 to 158 °F (–40 to 70 °C)
With Integral Display: –4 to 131 °F (–20 to 55 °C)
Enclosure rating: NEMA 4X, CSA Type 4X, IP 66
Because the frequency of the gauges is within a communication
bandwidth, they must comply with telecommunication requirements. To
meet most of these requirements, the APEX and APEX Sentry Radar
Gauges must be installed on enclosed or vented metal tanks. However,
other tank types may be approved in country of final destination. Refer to
“Telecom Restrictions” on page A-2 for detailed information.
Process Conditions APEX and APEX Sentry
Suitable for liquids, slurries, or sludges
Nozzle Temperature Range: –40 to 374 °F (–40 to 190 °C) See chart on
next page
Process Pressure Range: full vacuum to 155 psi (10,69 bar) See chart on
next page.
ELECTRICAL
SPECIFICATIONS
APEX and APEX Sentry
Gauge entry is ¾–14 NPT female conduit fittings
Gauge is factory sealed; conduit seal not required to meet FM
explosion-proof requirements
Terminal block provides connections for AC or DC power (specified at time
of order) and grounding
Transient protection: APEX and APEX Sentry Radar Gauges comply with
IEC standard 61000 4-5
Connections for secondary inputs and loop testing available on APEX only