Cerabar S/Deltabar S Description of parameters (ToF Tool)
Endress+Hauser 127
FLOW-MEAS. TYPE
Selection
Select the flow type.
Options:
• Volume p. cond. (volume under operating conditions)
• Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0 °C))
• Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar
(14.7 psi) and 288.15 K (15 °C/59 °F))
• Mass p. cond. (mass under operating conditions)
Factory setting:
Volume p. cond.
UNIT FLOW
Selection
Select volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = volume p. cond.
Options:
• m3/s, m3/min, m3/h, m3/day
• l/s, l/min, l/h
• hl/s, hl/min, hl/day
• ft3/s, ft3/min, ft3/h, ft3/day
• ACFS, ACFM, ACFH, ACFD
• ozf/s, ozf/min
• US Gal/s, US Gal/min, US Gal/h, US Gal/day
• Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
• bbl/s, bbl/min, bbl/h, bbl/day
•User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
m
3
/s
NORM FLOW UNIT
Selection
Select norm volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = gas norm conditions
Options:
• Nm3/s, Nm3/min, Nm3/h, Nm3/day
•User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
Nm
3
/s
STD. FLOW UNIT
Selection
Select standard volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = gas std. conditions
Options:
• Sm3/s, Sm3/min, Sm3/h, Sm3/day
• SCFS, SCFM, SCFH, SCFD
•User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
Sm
3
/s
ToF Tool, Table 10: OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name Description