Description of parameters (ToF Tool) Cerabar S/Deltabar S
130 Endress+Hauser
TEMP. ENG. UNIT
Selection
Select the unit for the temperature measured values.
See also PCB TEMPERATURE (Page 139) and SENSOR TEMP. (Page 143).
Options:
•°C
•°F
•K
•R
Factory setting:
°C
ADJUST DENSITY
Entry
Enter density of fluid.
Factory setting:
1.0
PROCESS DENSITY
Entry
Enter a new density value for density correction.
The calibration was carried out with the medium water, for example. Now the container
is to be used for another fluid with another density. The calibration is corrected
appropriately by entering the new density value in the PROCESS DENSITY parameter.
Factory setting:
1.0
ToF Tool, Table 13: OPERATING MENU SETTINGS EXTENDED SETUP "Flow"
Parameter name Description
Prerequisite:
•MEASURING MODE = flow
Note:
See also Page 89 ff, Section 9 "Flow measurement".
TEMP. ENG. UNIT
Selection
Select the unit for the temperature measured value.
See also PCB TEMPERATURE (Page 139) and SENSOR TEMP. (Page 144).
Options:
•°C
•°F
•K
•R
Factory setting:
°C
LOW FLOW CUT-OFF
Selection
Switches "low flow cut-off" function on and off.
In the lower measuring range, small flow quantities (creepages) can lead to large
measured value fluctuations. Switching on this function stops these flow quantities from
being recorded. See also SET. L. FL. CUT-OFF.
Options:
•Off
•On
Factory setting:
Off
ToF Tool, Table 12: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
Parameter name Description