Cerabar S/Deltabar S Trouble-shooting
Endress+Hauser 153
700 (W700) Warning
C
C>Last configuration not
stored
23 11 An error occurred when writing
or reading configuration data or
the power supply was
disconnected.
Perform reset (Code 7864) and
carry out calibration again.
53
Main electronics defect. Replace main electronics.
702 (W702) Warning
C
C>HistoROM data not
consistent.
17 11 Data were not written correctly
to the HistoROM, e.g. if the
HistoROM was detached during
the writing process.
Repeat upload.
Perform reset (Code 7864) and
carry out calibration again.
54
HistoROM does not have any
data.
Copy suitable data to the
HistoROM. (See also
Operating Instructions BA301P
(Deltabar S) or BA302P
(Cerabar S), Section 5.4.1
"Copying configuration data".)
703 (A703) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
23
Main electronics defect. Replace main electronics.
704 (A704) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
13
Main electronics defect. Replace main electronics.
705 (A705) Alarm
B
B>Measurement error 20 5 Fault in the main electronics. Briefly disconnect device from
the power supply.
22
Main electronics defect. Replace main electronics.
706 (W706) Warning
C
C>Configuration in
HistoROM and device
not identical
23 11 Configuration (parameters) in
the HistoROM and in the device
is not identical.
Copy data from the device to
the HistoROM. (See also
Operating Instructions BA301P
(Deltabar S) or BA302P
(Cerabar S), Section 5.4.1
"Copying configuration data".)
Copy data from the HistoROM
to the device. (See also
Operating Instructions BA301P
(Deltabar S) or BA302P
(Cerabar S), Section 5.4.1
"Copying configuration data".)
The message remains if the
HistoROM and the device have
different software versions. The
message goes out if you copy the
data from the device to the
HistoROM.
59
707 (A707) Alarm
B
B>X-VAL. (TAB_XY
_VALUE) of lin. table out
of edit limits.
18 8 At least one X-VALUE
(TAB_XY_VALUE) in the
linearisation table is either
below the value for SCALE_IN,
EU_0/HYDR. PRESS MIN. or
LINEAR_ LEVEL_MIN/MIN.
LEVEL or above the value for
SCALE_IN, EU_100/HYDR.
PRESS. MAX. or
LINEAR_LEVEL_MAX/LEVEL
MAX.
Carry out calibration again.
( See also these Operating
Instructions, chapter 4 and 8.)
38
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Value
Cause Measure Prio-
rity