Cerabar S/Deltabar S Trouble-shooting
Endress+Hauser 155
722 (A722) Alarm
B
B>EMPTY CALIB.
(SCALE_OUT, EU_0) or
FULL CALIB.
(SCALE_OUT, EU_100)
out of edit limits
18 8 LINEAR_ LEVEL_MIN/LEVEL
MIN or LINEAR_LEVEL_MAX/
LEVEL MAX has been changed.
Perform reset (Code 2710) and
carry out calibration again.
42
723 (A723) Alarm
B
B>MAX. FLOW
(SCALE_OUT, EU_100)
out of edit limits
18 8 FLOW_TYOPE/FLOW-MEAS.
TYPE has been changed.
Carry out calibration again. 43
725 (A725) Alarm
B
B>Sensor connection
error, cycle disturbance
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI382P (Deltabar S) or TI383P
(Cerabar S).
Block off electromagnetic effects
or eliminate source of
disturbance.
26
Sensor or main electronics
defect.
Replace sensor or main
electronics.
726 (E726) Error
C
C>Sensor temperature
error - overrange
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI382P (Deltabar S) or TI383P
(Cerabar S).
Block off electromagnetic effects
or eliminate source of
disturbance.
32
Process temperature is outside
permitted range.
Check temperature present,
reduce or increase if necessary.
Sensor defect. If the process temperature is
within the permitted range,
replace sensor.
727 (E727) Error
C
C>Sensor pressure error
- overrange
20 5 Electromagnetic effects are
greater than specifications in the
technical data.
See Technical Information
TI382P (Deltabar S) or TI383P
(Cerabar S).
Block off electromagnetic effects
or eliminate source of
disturbance.
29
Pressure is outside permitted
range.
Check pressure present, reduce
or increase if necessary.
Sensor defect. If the pressure is within the
permitted range, replace sensor.
728 (A728) Alarm
B
B>RAM error 20 9 Fault in the main electronics. Briefly disconnect device from
the power supply.
2
Main electronics defect. Replace main electronics.
729 (A729) Alarm
B
B>RAM error 20 9 Fault in the main electronics. Briefly disconnect device from
the power supply.
3
Main electronics defect. Replace main electronics.
730 (E730) Error
C
C>LRV user limits
exceeded
19 8 Pressure measured value has
undershot the value specified for
the PRESSURE_1_USER_
LOW_LIMIT/Pmin ALARM
WINDOW parameter.
Check system/pressure
measured value.
Change value for
PRESSURE_1_USER_ LOW_
LIMIT/Pmin ALARM
WINDOW if necessary. (See
also Page 63 and Page 150.)
47
Code Error
type/
NA 64
Message/description XD_
ERROR
Value
BLOCK_
ERROR
Value
Cause Measure Prio-
rity