Cerabar S/Deltabar S Description of parameters (FF configuration program)
Endress+Hauser 63
CHOOSE_ERROR_OR_
WARNING/
SELECT ALARM TYPE
Entry
Index: 21
Data type: Unsigned8
Access: Auto, OOS
For "Error"-type messages, you can decide whether the device should behave as in the event
of an alarm (A) or as in the event of a warning (W). See also
REACTION_ON_ALARM_NR/ERROR NO.
See also these Operating Instructions, Section 11.2 "Response of outputs to errors".
Options:
Alarm (A): The primary value is transmitted with the status BAD.
Warning (W): device continues measuring. The primary value is transmitted with the
status UNCERTAIN.
Operation:
1. Enter the appropriate message number by means of the REACTION_ON_ALARM_NR/
ERROR NO. parameter.
2. Select the "Alarm" or "Warning" option by means of the
CHOOSE_ERROR_OR_WARNING/SELECT ALARM TYPE parameter.
!
Note!
You can carry out dialog-guided configuration of the "error"-type messages by means of the
"Select Alarmtype" method in the Diagnostic Transducer Block.
ALARM SETUP TIME/
ALARM DELAY
Entry
Index: 22
Data type: Float
Access: Auto, OOS
Enter alarm response time.
!
Note!
There is no alarm if the cause of the error is eliminated within the alarm delay time.
Input range:
0...100 s
Factory setting:
0.0 s
ALARM HOLD TIME/
ALARM DISPL. TIME
Entry
Index: 23
Data type: Float
Access: Auto, OOS
Enter alarm display time. Once the cause of the error is rectified, the alarm display time starts
running.
!
Note!
The following applies for the setting ACKNOWLEDGE_ALARM_MODE/ACK. ALARM
MODE = On:
If an alarm appears and the alarm display time elapses before the alarm has been
acknowledged, the message will be cleared once it has been acknowledged.
See also these Operating Instructions, Section 11.3 "Confirming messages".
Input range:
0...999.9 s
Factory setting:
0.0 s
PRESSURE_1_UNIT/
PRESS. ENG. UNIT
Display
Index: 24
Data type: Unsigned16
Access: Read only
Displays the pressure unit selected.
The pressure unit is selected by means of the CAL_UNIT parameter ( Page 34) in the
Pressure Transducer Block.
PRESSURE_1_USER_
LOW_LIMIT/
Pmin ALARM WINDOW
Entry
Index: 25
Data type: Float
Access: Auto, OOS
Customer-specific process monitoring – enter lower pressure limit.
You can use the REACTION_ON_ALARM_NR/SELECT ALARM TYPE parameter to enter
how the device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", Table, Code E730 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Lower measuring limit •1.1
(For the lower measuring limit, see SENSOR_RANGE, element EU_0, Page 34.)
PRESSURE_1_USER_
HIGH_LIMIT/
Pmax ALARM WINDOW
Entry
Index: 26
Data type: Float
Access: Auto, OOS
Customer-specific process monitoring – enter upper pressure limit.
You can use the REACTION_ON_ALARM_NR/SELECT ALARM TYPE parameter to enter
how the device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", Table, Code E731 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Upper measuring limit • 1.1
(For the upper measuring limit, see SENSOR_RANGE, element EU_100, Page 34.)
Diagnosis Transducer Block
Parameter Description