Description of parameters (FF configuration program) Cerabar S/Deltabar S
64 Endress+Hauser
TEMPERATURE_UNIT/
TEMP. ENG. UNIT
Display
Index: 27
Data type: Unsigend16
Access: Read only
Displays the temperature unit selected.
The temperature unit is selected by means of the SECONDARY_VALUE_UNIT parameter
( Page 35) in the Pressure Transducer Block.
TEMPERATURE_1_
USER_LOW_LIMIT/
Tmin ALARM WINDOW
Entry
Index: 28
Data type: Float
Access: Auto, OOS
Customer-specific process monitoring – enter lower temperature limit.
You can use the REACTION_ON_ALARM_NR/SELECT ALARM TYPE parameter to enter
how the device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", Table, Code E732 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Lower sensor temperature operating limit – 10 K
(for the lower temperature operating limit, see TEMPERATURE_1_SENSOR_LIMIT_
LOW/Tmin SENSOR, Page 53)
TEMPERATURE_1_
USER_HIGH_LIMIT/
Tmax ALARM WINDOW
Entry
Index: 29
Data type: Float
Access: Auto, OOS
Customer-specific process monitoring – enter upper temperature limit.
You can use the REACTION_ON_ALARM_NR/SELECT ALARM TYPE parameter to enter
how the device responds if the operating pressure undershoots the specified value.
See also these Operating Instructions, Section 11.1 "Messages", Table, Code E733 and
Section 11.2. "Response of outputs to errors".
Factory setting:
Upper sensor temperature operating limit +10 K
(for the upper temperature operating limit, see TEMPERATURE_1_SENSOR_LIMIT_
HIGH/Tmax SENSOR, Page 53)
RESET_INPUT_VALUE/
ENTER RESET CODE
Entry
Index: 30
Data type: Unsigned16
Access: Auto, OOS
Reset parameters completely or partially to factory values or delivery status.
See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S), Section 5.7
"Factory setting" (reset).
Factory setting:
0
OPERATING_HOURS
Display
Index: 31
Data type: Unsigned32
Access: Read only
Displays the hours of operation. This parameter cannot be reset.
ALARM_TABLE_ARRAY
/ALARM TABLE ENTRY
Display
Index: 32
Data type: Visible String
Access: Read only
This parameter displays pending alarms and warnings in hexadecimal numerical format
(max. 16). Every message is assigned to a bit in the sequence of the error code in accordance
with Section 11.1 "Messages".
Diagnosis Transducer Block
Parameter Description