Cerabar S/Deltabar S Description of parameters (FF configuration program)
Endress+Hauser 47
FLOW_UNIT/
UNIT FLOW
Entry
Index: 69
Data type: Unsigned16
Access: Auto, OOS
Select flow unit.
Prerequisite:
• Deltabar S differential pressure transmitter
!
Note!
Make sure the unit suits the flow mode selected. → See also Page 46, parameter description
for FLOW_TYPE/ FLOW-MEAS. TYPE.
When a new flow unit is selected, all flow-specific parameters are converted and displayed
with the new unit within a flow mode (FLOW_UNIT/ FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Possible units for FLOW_UNIT/FLOW TYPE = volume p. cond.:
• m3/s, m3/min, m3/h, m3/day
• l/s, l/min, l/h
• hl/s, hl/min, hl/day
• ft3/s, ft3/min, ft3/h, ft3/day
• ACFS, ACFM, ACFH, ACFD
• ozf/s, ozf/min
• US Gal/s, US Gal/min, US Gal/h, US Gal/day
• Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
• bbl/s, bbl/min, bbl/h, bbl/day
•User unit, → See also parameter descriptions for FLOW_UNIT_TEXT/CUSTOMER
UNIT F (Page 48) and FLOW_UNIT_SCALE/CUST. UNIT FACT. F (Page 48).
Factory setting:
m
3
/s
Possible units for FLOW_UNIT/ FLOW-MEAS. TYPE = gas norm cond.:
• Nm3/s, Nm3/min, Nm3/h, Nm3/day
•User unit, → See also parameter descriptions for FLOW_UNIT_TEXT/CUSTOMER
UNIT F (Page 48) and FLOW_UNIT_SCALE/CUST. UNIT FACT. F (Page 48).
Factory setting:
Nm
3
/s
Possible units for FLOW_UNIT/ FLOW-MEAS. TYPE = gas std. cond.:
• Sm3/s, Sm3/min, Sm3/h, Sm3/day
• SCFS, SCFM, SCFH, SCFD
•User unit, → See also parameter descriptions for FLOW_UNIT_TEXT/CUSTOMER
UNIT F (Page 48) and FLOW_UNIT_SCALE/CUST. UNIT FACT. F (Page 48).
Factory setting:
Sm
3
/s
Possible units for FLOW_UNIT/FLOW-MEAS. TYPE = mass p. cond.:
• g/s, kg/s, kg/min, kg/min, kg/h
• t/s, t/min, t/h, t/day
•oz/s, oz/min
• lb/s, lb/min, lb/h
• ton/s, ton/min, ton/h, ton/day
•User unit, → See also parameter descriptions for FLOW_UNIT_TEXT/CUSTOMER
UNIT F (Page 48) and FLOW_UNIT_SCALE/CUST. UNIT FACT. F (Page 48).
Factory setting:
kg/s