Gammapilot FMG50 Commissioning
Endress+Hauser 67
2. Perform linearization
A0042219
The individual linearization values are entered via the input screen or via a
separate linearization module.
The linearization table consists of up to 32 "density value : concentration (%)"
value pairs.
3. The table values can be sorted as monotonically decreasing using the "Table mode ->
Sort table" function.
Edit table: the index of the linearization point is entered in this field (1-32
points)
Customer input value: enter the customer density
Customer value: level in unit of length, volume unit or %.
Activate table: the "Enable" option must first be selected before the linearization
table is used. The linearization table is not used as long as "Disable" is selected.
4. The linearization table can also be entered manually in the linearization module. This
is started by selecting the "Linearization" button:
A0042194
The normalized pulse rate and the customer value can be entered directly in table
form in this module.
The linearization table must be activated by selecting "Activate table" = Enable
TIP: if the density adjustment is already completed in the Wizard, it is no longer
displayed. The operating mode must be temporarily set to "Density" in the Wizard
to be able to perform the density adjustment again or to recalibrate.