Installation Gammapilot M FMG60 with FOUNDATION Fieldbus
16 Endress+Hauser
In cascading mode no gap should occur between the measuring ranges of the different
Gammapilot M.
The source container and the Gammapilot M must be mounted as close to the vessel as possible.
Any access to the beam must be blocked so that no persons or part of their body (hand, arm, head)
may come into the area of the beam.
In order to enlarge the lifetime, the Gammapilot M should be protected against direct sun. If
necessary, a protective cover should be applied.
The mounting device FHG60 (see chapter "Accessories) or an equivalent mounting device should
be used for fastening the Gammapilot M.
The mounting device must be installed in a way such that it can withstand the weight of the
Gammapilot M
1)
under all operating conditions (e.g. vibrations).
!
Note!
The Gammapilot M should be given additional support to prevent damage to the connecting cable
or to the unit if it falls off.
Examples
L00-FMG60xxx-17-00-00-xx-001
1: Vertical cylinder; the Gammapilot M is mounted vertically with the detector head pointing downwards; the gamma ray
is aligned to the measuring range. 2: Cascading of multiple Gammapilot M; there is no gap between the measuring ranges.
3: Conical tank outlet (here with sun protection cover); 4: Horizontal cylinder (here with sun protection cover); 5: Wrong:
Gammapilot M mounted inside the tank insulation; 6: Right: Tank insulation removed for Gammapilot M; 7: Support.
1) The weights of the various versions of the Gammapilot M are summarized in the section "Dimensions/Weight".