Technical data Gammapilot M FMG60 with FOUNDATION Fieldbus
98 Endress+Hauser
10 Technical data
10.1 Technical data at a glance
10.1.1 Input
Measured variable The Gammapilot M measures the pulse rate (number of counts per second). This rate is proportional
to the intensity of radiation at the detector. From this rate, the Gammapilot M calculates the desired
measured value:
Level limit (0% = "radiation path free"; 100% = "radiation path covered")
Level (in %)
Position of interface (in %)
Density (unit selectable)
Concentration (unit selectable)
Pulse rate:
Max. 45000 c/s per individual unit
Max. 65000 c/s cascade
Temperature input (PT 100)
for density measurements
In order to compensate temperature influences on the density measurements a temperature sensor
PT 100 (4-wire connection) can be connected.
Measuring range: -40 °C to 200 °C
Accuracy: ±1 K
10.1.2 Output
Output signal FOUNDATION Fieldbus (FF)
Pulses for cascading mode
Output damping Freely selectable, 1 to 999 s
10.1.3 Characteristic quantities of the Foundation Fieldbus interface
Terminal voltage The following values are the voltages across the terminals directly at the device:
Current consumption 11 mA ± 1 mA
Type Minimum
terminal voltage
Maximum
terminal voltage
standard 9 V 32 V
EEx ia (FISCO model) 9 V 17.5 V
EEx ia (Entity concept) 9 V 24 V