Gammapilot M FMG60 with FOUNDATION Fieldbus Installation
Endress+Hauser 15
3.2 Installation conditions
3.2.1 Dimensions, weight
Gammapilot M (without water cooling jacket)
L00-FMG60xxx-06-00-00-xx-001
Gammapilot M with water cooling jacket or collimator
L00-FMG60xxx-06-00-00-xx-002
3.2.2 Installation conditions for level measurement
Conditions
For level measurements the Gammapilot M is mounted vertically; if possible the detector head
should point downwards.
The exit angle of the source container must be exactly aligned to the measuring range of the
Gammapilot M. Observe the measuring range marks of the Gammapilot M.
Type
Measuring
length A
[mm]
without water cooling
jacket
with water cooling jacket
Overall
length
B [mm]
Weight
[kg]
Overall
length
B [mm]
Weight
without water
[kg]
Weight
including
water
[kg]
NaI 50 621 14 631 18 20
NaI with collimator 50 663 35
PVT 200 780 15 790 20 24
PVT 400 980 16 990 23 29
PVT 800 1380 20 1390 31 40
PVT 1200 1780 24 1790 37 50
PVT 1600 2180 28 2190 45 61
PVT 2000 2580 31 2590 51 72
160 x 190
Æ 120
Æ 80
537
A
B
160 x 190
537
A
B
164
12
Ø140