Operation Gammapilot M FMG60 with FOUNDATION Fieldbus
54 Endress+Hauser
Simulation
The SIMULATE parameter allows the Transducer block output value to be simulated, provided
simulation has also been enabled at the device DIP switch. The simulation must be enabled, a value
and/or status entered and the block must be in AUTO mode. During simulation the Transducer
block output value is substituted by the simulated value.
A simulation is also possible by switching MODE_BLK to "MAN" and entering a value for OUT.
Parameter Description
SIMULATE Enables, sets and displays a simulated value, options:
–enable/disable
– simulated value
–output value