Accessories Gammapilot M FMG60 with FOUNDATION Fieldbus
92 Endress+Hauser
8.4.2 Application hints
L00-FMG60xxx-17-00-00-xx-008
Mounting position: ➀ preferred; ➁ alternative
A: Level measurement, FMG60 without water jacket; B: Level measurement, FMG60 with water jacket;
C: Level limit measurement, FMG60 without water jacket; D: Level limit measurement, FMG60 with water jacket;
E: Such horizontal mounting not permitted
(a): Retainer for pipe ∅ 80 mm; (b): Retainer for pipe ∅ 102 mm; (c): Retainer for water cooling jacket, ∅140 mm; (d):
Bracket
"
Caution!
• The mounting device must be fitted in a way such that it can withstand the weight of the
Gammapilot M under all operating conditions to be expected.
• For a measuring length of 1600 mm or more, two retainers (vertical) or three retainers
(horizontal) must be used.
• For vertical mounting usage of the bracket or a support unit fitted by the customer is mandatory.
Otherwise a sufficient stability and support of the Gammapilot M is not ensured.
• For stability reasons the mounting version with the compartment housing pointing upwards
should only be used in exceptional cases(e.g. lack of space).
• To prevent damage of the detector tube, the maximum torque of the retainer screws is 6 Nm.
8.4.3 ordering information for complete mounting set FHG60
(a) (c)
(a) (c)
(a)
(c)
(a)
(c)
(b)
(a)
(c) (c)
A
1
1
22
BC
D
(d)
(d)
(d)
(d)
(a)
E
(a)
Application
1 Level, measuring range of FMG60: 400-1200 mm; (1 bracket, 1 retainer)
2 Level, measuring range of FMG60: 1600-2000 mm; (1 bracket, 2 retainers)
3 Level limit, measuring range of FMG60: 200/400 mm; (2 retainers)
9 Special version, to be specified
Mounting clamp
A FMG60 without water cooling
B FMG60 with water cooling
Y Special version, to be specified
Material
1 316L
9 Special version, to be specified
FHG60 - Complete product designation