Micropilot FMR56, FMR57 FOUNDATION Fieldbus Operating menu
Endress+Hauser 135
User interface Init. recording
In progress
Finished
17.3.2 "Analog input 1 to 5" submenu
There is an Analog inputs submenu for every AI block of the device. The AI block is used
to configure the measured value transmission to the bus.
Only the most basic properties of the AI block can be configured in this submenu. For
a detailed configuration of the AI blocks refer to the Expert menu.
Navigation  Setup → Analog inputs → Analog input 1 to 5
Block tag
Navigation  Setup → Analog inputs → Analog input 1 to 5 → Block tag
Description Defined to be unique throughout the control system at one plant site. The tag may be
changed using the FB_Tag service.
Factory setting
Channel
Navigation  Setup → Analog inputs → Analog input 1 to 5 → Channel
Description Use this function to select the input value that should be processed in the analog input
function block.
Selection Uninitialized
Level linearized
Absolute echo amplitude
Distance
Electronic temperature
Relative echo amplitude
Analog output adv. diagnostics 1
Analog output adv. diagnostics 2
Terminal voltage
Factory setting Uninitialized