Commissioning (block-based operation) Micropilot FMR56, FMR57 FOUNDATION Fieldbus
84 Endress+Hauser
12.5 Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via
the SETUP (TRDSUP) Transducer Block.
A0016934
R = Reference point of the measurement E = Empty calibration (= Zero point)
D = Distance F = Full calibration (= span)
L = Level
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit (distance_unit) Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: ft
• 1019: in
2 SETUP (TRDSUP) Bin type (bin_type) Select bin type.
Selection:
• 734: Workbench test
• 1275: Bin/pile
• 1276: Buffer silo (fast)
• 1277: Crusher/belt
• 1278: Silo
3 SETUP (TRDSUP) Max. filling speed solid
(solid_filling_sped_range)
Select maximum expected filling speed.
Auswahl:
• 723: Very slow < 0,5m (1.6ft) /h
• 724: Slow < 1 m (3.3ft) /h
• 725: Medium < 4m (13ft) /h
• 726: Fast < 8m (26ft) /h
• 727: Very fast > 8m (26ft) /h
• 33442: No filter / test
4 SETUP (TRDSUP) Max draining speed solid
(solid_draining_sped_range)
Select maximum expected draining speed.
Auswahl:
• 723: Very slow < 0,5m (1.6ft) /h
• 724: Slow < 1 m (3.3ft) /h
• 725: Medium < 4m (13ft) /h
• 726: Fast < 8m (26ft) /h
• 727: Very fast > 8m (26ft) /h
• 33442: No filter / test