Integration into a FOUNDATION Fieldbus network Micropilot FMR56, FMR57 FOUNDATION Fieldbus
64 Endress+Hauser
9.4.2 Block configuration when device is delivered
DIAGNOSTIC
PID ARITHMETIC SIGNAL_CHAR
S
RESOURCE
ANALOG_INPUT_1
ANALOG_INPUT_2
DI
ADV_SETUP
DATA_TRANSFER
EXPERT_INFO
SERVICE_INFO
DISPLAY
INPUT_SELECTOR
INTEGRATOR ANALOG_ALARM
EXPERT_CONFIG
SETUP
SERVICE_SENSOR
PV
SV
ESC
OPEN
OPEN
E
Device_01 F
mm
4841.000
A0017217
19 Block configuration when device is delivered
S Sensor
PV Primary value: Level linearized
SV Secondary value: Distance
9.5 Assignment of the measured values (CHANNEL) in
an AI Block
The input value of an Analog Input Block is defined by the CHANNEL parameter.
Channel Measured value
0 Uninitialized
211 Terminal voltage
773 Analog output advance diagnostics 1
774 Analog output advance diagnostics 2
32786 Absolute echo amplitude
32856 Distance
32885 Elektronic temperature
32949 Level linearized
33044 Relative echo amplitude
9.6 Index tables of Endress+Hauser parameters
The following tables list the manufacturer-specific device parameters for the Resource
Blocks. For the FOUNDATION Fieldbus parameters, see the document BA062S "Guidline -
FOUNDATION Fieldbus Function Blocks", which can be downloaded from
www.endress.com.