Operating menu Micropilot FMR56, FMR57 FOUNDATION Fieldbus
152 Endress+Hauser
Factory setting 0 %
Level (Semiautomatic)
Navigation Setup → Advanced setup → Linearization → Level
Prerequisite • Linearization type (→ 146) = Table
• Table mode (→ 150) = Semiautomatic
Description Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Navigation Setup → Advanced setup → Linearization → Customer value
Prerequisite Linearization type (→ 146) = Table
Description Enter linearized value for the table point.
User entry Signed floating-point number
Factory setting 0 %
Activate table
Navigation Setup → Advanced setup → Linearization → Activate table
Prerequisite Linearization type (→ 146) = Table
Description Activate (enable) or deactivate (disable) the linearization table.
Selection • Disable
• Enable
Factory setting Disable
Additional information Meaning of the options
• Disable
The measured level is not linearized.
If Linearization type (→ 146) = Table at the same time, the device issues error
message F435.
• Enable
The measured level is linearized according to the table.
When editing the table, the Activate table parameter is automatically reset to
Disable and must be reset to Enable after the table has been entered.