Micropilot FMR56, FMR57 FOUNDATION Fieldbus Operating menu
Endress+Hauser 159
A0015586
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
Switch-on delay
Navigation Setup → Advanced setup → Switch output → Switch-on delay
Prerequisite • Switch output function (→ 156) = Limit
• Assign limit (→ 157) ≠ Off
Description Define switch-on delay.
User entry 0.0 to 100.0 s
Factory setting 0.0 s
Switch-off value
Navigation Setup → Advanced setup → Switch output → Switch-off value
Prerequisite Switch output function (→ 156) = Limit
Description Enter measured value for the switch-off point.
User entry Signed floating-point number
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters; description: see the Switch-on value parameter
(→ 158).