Commissioning (block-based operation) Micropilot FMR56, FMR57 FOUNDATION Fieldbus
88 Endress+Hauser
12.8.1 Groups of events
The diagnostic messages are classified into 16 groups according to the source and severity
of the respective event. A default diagnostic category is allocated to each group. Each
group is also represented by one bit of the allocation parameters.
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
Highest severity Failure (F) Sensor 31 F003: Broken probe detected
F046: Build-up detected
F083: Memory content
F104: HF cable
F105: HF cable
F106: Sensor
Electronics 30 F242: Software incompatible
F252: Modules incompatible
F261: Electronic modules
F262: Module connecting
F270: Main electronic failure
F271: Main electronic failure
F272: Main electronic failure
F273: Main electronic failure
F275: I/O-Modul failure
F276: I/O module failure
F282: Data storage
F283: Memory content
F311: Electronic Failure
Configuration 29 F410: Data transfer
F435: Linearization
F437: Configuration incompatible
F482: Block in OOS
Process 28 F803: Current loop 1
F825: Current loop 1
F936: EMC interference
F941: Echo lost
1)
F970: Linearization
1) This event can be removed from the group in order to define its behavior individually; see section
"Configurable area".
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
High severity Function check (C) Sensor 27 not used in Micropilot
Electronics 26 not used in Micropilot
Configuration 25 C411: Up-/download
C484: Simulation failure mode
C485: Simulation measured value
C492: Simulation frequency
output
C493: Simulation pulse output
C494: Switch output simulation
C495: Simulation block output
C585: Simulation distance
C586: Record map
Process 24 not used in Micropilot
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
Low severity Out of specification (S) Sensor 23 not used in Micropilot
Electronics 22 not used in Micropilot

Table of Contents