Micropilot FMR56, FMR57 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 87
12.8 Configuration of the event behavior according to the
FOUNDATION Fieldbus specification FF912
The device complies with the FOUNDATION Fieldbus specification FF912. This has -
among other things - the following consequences:
The diagnsotic category according to NAMUR recommendation NE107 is transmitted via
the fieldbus in a manufacturer-independent form:
F: Failure
C: Function check
S: Out of specification
M: Maintenance required
The diagnostic category of pre-defined groups of events can be adjusted by the user
according to the requirements of the specific application.
Certain events can be separated from their group and can be handled individually:
941: Echo lost
942: In safety distance
950: Advanced Diagnostic occurred
Additional information and remedial measures are transmitted together with the event
message via the fieldbus.
The diagnostic messages according to FF912 are available in the host only if the
Multi-bit support option has been activated in the FEATURE_SEL parameter of the
Resource block. For reasons of compatibility, this option is not activated on delivery: