Commissioning (block-based operation) Micropilot FMR56, FMR57 FOUNDATION Fieldbus
86 Endress+Hauser
Functions of the parameter options
Options Description
33097: Execute backup A backup copy of the current device configuration in the HistoROM is saved to the
display module of the device. The backup copy comprises the transmitter data of
the device.
33057: Restore The last backup copy of the device configuration is copied from the display module
to the HistoROM of the device. The backup copy comprises the transmitter data of
the device.
33838: Duplicate The transmitter configuration from another device is duplicated to the device using
the display module.
265: Compare The device configuration saved in the display module is compared to the current
device configuration of the HistoROM.
32848: Clear backup data The backup copy of the device configuration is deleted from the display module of
the device.
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.