Integration into a FOUNDATION Fieldbus network Micropilot FMR56, FMR57 FOUNDATION Fieldbus
68 Endress+Hauser
Name Label Index Data type Size (Bytes) Storage Class Write access MODE_BLK
diag_4_timestamp Timestamp 28 STRING 14 Dynamic
diagnostics_5 Diagnostics 5 29 UINT32 4 Dynamic
diag_5_timestamp Timestamp 30 STRING 14 Dynamic
filter_options Filter options 31 ENUM8 1 Static Maintenance AUTO
clear_event_list Clear event list 32 ENUM16 2 Static Service AUTO
simulation_distance_ro Simulation distance 33 ENUM16 2 Static Development AUTO
value_of_simulated_distan
ce
Vaue of simulated distance 34 FLOAT 4 Static Maintenance AUTO
assign_sim_meas Assign measurement
variable
35 ENUM16 4 Static Maintenance OOS
sim_value_process_variabl
e
Value process variable 36 FLOAT 4 Static Maintenance OOS
switch_output_simulation Switch output simulation 37 ENUM16 2 Static Maintenance OOS
sim_switch_status Switch status 38 ENUM16 2 Static Maintenance AUTO
simulation_device_alarm Simulation device alarm 39 ENUM16 2 Static Maintenance OOS
simulation_diagnostic_eve
nt
Simulation diagnostic event 40 UINT32 4 Static Service OOS
start_device_check Start device check 41 ENUM16 2 Static Maintenance AUTO
result_device_check Result device check 42 ENUM16 2 Static Development AUTO
last_check_time Last check time 43 STRING 14 Dynamic
level_signal Level signal 44 ENUM16 2 Static Development AUTO
device_check_timestamp Timestamp 45 UINT32 14 Static Development AUTO
assign_channel_1 Assign channel 1 54 ENUM16 2 Static Maintenance AUTO
assign_channel_2 Assign channel 2 55 ENUM16 2 Static Maintenance AUTO
assign_channel_3 Assign channel 3 56 ENUM16 2 Static Maintenance AUTO
assign_channel_4 Assign channel 4 57 ENUM16 2 Static Maintenance AUTO
logging_interval Logging interval 58 FLOAT 4 Static Maintenance AUTO
clear_logging_data Clear logging data 59 ENUM16 2 Static Maintenance AUTO
alarm_delay Alarm delay 60 FLOAT 4 Static Maintenance AUTO
9.6.5 Expert Configuration Transducer Block
The parameters of the Expert Configuration Transducer Block are described in
GP01017F: "Micropilot FMR5x - Description of Device Parameters - FOUNDATION
Fieldbus"
Name Label Index Data type Size (Bytes) Storage Class Write access MODE_BLK
locking status Locking status 15 ENUM16 2
access_status_tooling Access status tooling 16 ENUM16 2
enter_access_code Enter access code 17 UINT16 2 Static Operator AUTO
distance_unit_ro Distance unit 18 ENUM16 2 Static Maintenance OOS
operating_mode_ro Operating mode 19 ENUM16 2 Static Maintenance OOS
free_field_special Free field special 20 ENUM16 2 Static Maintenance OOS
sensor_type Sensor type 21 ENUM16 2 Static Service OOS
distance_offset Distance offset 22 FLOAT 4 Static Maintenance OOS
level_unit_ro Level unit 23 ENUM16 2 Static Maintenance OOS