Operating menu Micropilot FMR56, FMR57 FOUNDATION Fieldbus
142 Endress+Hauser
Additional information The value specified in this parameter is added to the measured level (before linearization).
Tank/silo height
Navigation Setup → Advanced setup → Level → Tank/silo height
Description Specify total height of the tank or silo as measured from the process connection.
User entry –999.9999 to 999.9999 m
Factory setting Empty calibration (→ 128)
Additional information If the parametrized measuring range (Empty calibration (→ 128)) differs significantly
from the tank or silo height, it is recommended to enter the tank or silo height. Example:
Continuous level monitoring in the upper third of a tank or silo.
A0019868
35 '"Tank/silo height" parameter (→ 142)' for measurements in bulk solids
E Empty calibration (→ 128)
1 Tank/silo height (→ 142)
For tanks with conical outlet, Tank/silo height should not be changed as in this type
of applications Empty calibration (→ 128) is usually not << the tank or silo
height.