Operating menu Micropilot FMR56, FMR57 FOUNDATION Fieldbus
128 Endress+Hauser
Selection • Very slow < 0,5m (1,6ft) /h
• Slow < 1m (3,3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting Standard < 2m (6,5ft) /h
Additional information It is strongly recommended to adjust this parameter to the actual maximum filling speed of
the process.
Max. draining speed solid
Navigation Setup → Max.drain solid
Prerequisite Medium type (→ 139) = Solid
Description Select expected maximum draining speed.
Selection • Very slow < 0,5m (1,6ft) /h
• Slow < 1m (3,3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting Standard < 2m (6,5ft) /h
Additional information It is strongly recommended to adjust this parameter to the actual maximum draining speed
of the process.
Empty calibration
Navigation Setup → Empty calibr.
Description Specify the distance E between the process connection and the minimum level (0%). This
defines the starting point of the measuring range.
User entry Depending on the antenna
Factory setting Depending on the antenna