Micropilot FMR56, FMR57 FOUNDATION Fieldbus Operating menu
Endress+Hauser 129
Additional information
A0019488
30 Empty calibration (E) for level measurements in bulk solids.
The measuring range starts at the point at which the radar beam hits the tank or silo
bottom. In the case of dished boiler ends or conical outlets levels below this point can
not be measured.
Full calibration
Navigation Setup → Full calibr.
Description Specify the distance F between the minimum level (0%) and the maximum level (100%).
User entry Depending on the antenna
Factory setting Depending on the antenna
Additional information
A0019489
31 Full calibration (F) for level measurements in bulk solids