Operating menu Micropilot FMR56, FMR57 FOUNDATION Fieldbus
150 Endress+Hauser
Additional information
0%
H
A0013264
H Intermediate height
The unit is defined in the Distance unit parameter (→  127).
Table mode
Navigation  Setup → Advanced setup → Linearization → Table mode
Prerequisite Linearization type (→  146) = Table
Description Select editing mode of the linearization table.
Selection Manual
Semiautomatic
*
Clear table
Sort table
Factory setting Manual
Additional information Meaning of the options
Manual
The level and the associated linearized value are entered manually for each linearization
point.
Semiautomatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
Clear table
Deletes the existing linearization table.
Sort table
Rearranges the linerization points into an ascending order.
* Visibility depends on order options or device settings