Operating menu Micropilot FMR56, FMR57 FOUNDATION Fieldbus
150 Endress+Hauser
Additional information
A0013264
H Intermediate height
The unit is defined in the Distance unit parameter (→ 127).
Table mode
Navigation Setup → Advanced setup → Linearization → Table mode
Prerequisite Linearization type (→ 146) = Table
Description Select editing mode of the linearization table.
Selection • Manual
• Semiautomatic
*
• Clear table
• Sort table
Factory setting Manual
Additional information Meaning of the options
• Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semiautomatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.