Micropilot FMR56, FMR57 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 91
Example
The Highest severity / Configuration group contains the messages 410: Data transfer,
411: Up-/Download, 435: Linearization and 437: Configuration incompatible. These
messages are no longer to be classified as Failure (F) but as Funcktion check (C).
1.
Use the FieldCare navigation window to navigate to the the following screen: Expert
→ Communication → Field diagnostics → Alarm detection enable.
2.
 24 Default state of the "Fail Map" and "Check Map" columns
Look for the Configuration Highest Severity group in the Fail Map column and
deactivate the associated checkbox (A). Activate the respective checkbox in the
Check Map column (B). Remember to confirm each change by pressing the Enter
key.