Micropilot FMR60B PROFINET with Ethernet-APL Technical data
Endress+Hauser 79
Restriction to a process temperature of 0 to +150 °C (+32 to +302 °F) with CSA C/US
approval and plastic housing
A0048826
33 Plastic housing; process temperature 0 to +150 °C (+32 to +302 °F) with CSA C/US approval
P1 = T
p
: 0 °C (+32 °F) | T
a
: +76 °C (+169 °F)
P2 = T
p
: +76 °C (+169 °F) | T
a
: +76 °C (+169 °F)
P3 = T
p
: +150 °C (+302 °F) | T
a
: +25 °C (+77 °F)
P4 = T
p
: +150 °C (+302 °F) | T
a
: 0 °C (+32 °F)
P5 = T
p
: 0 °C (+32 °F) | T
a
: 0 °C (+32 °F)
Plastic housing; process temperature –20 to +200 °C (–4 to +392 °F)
A0032024
34 Plastic housing; process temperature –20 to +200 °C (–4 to +392 °F)
P1 = T
p
: –20 °C (–4 °F) | T
a
: +76 °C (+169 °F)
P2 = T
p
: +76 °C (+169 °F) | T
a
: +76 °C (+169 °F)
P3 = T
p
: +200 °C (+392 °F) | T
a
: +27 °C (+81 °F)
P4 = T
p
: +200 °C (+392 °F) | T
a
: –20 °C (–4 °F)
P5 = T
p
: –20 °C (–4 °F) | T
a
: –20 °C (–4 °F)
In the case of devices with a plastic housing and CSA C/US approval, the selected
process temperature of –20 to +200 °C (–4 to +392 °F) is limited to
0 to +200 °C (+32 to +392 °F).
Restriction to a process temperature of 0 to +200 °C (+32 to +392 °F) with CSA C/US
approval and plastic housing
A0048826
35 Plastic housing; process temperature 0 to +200 °C (+32 to +392 °F) with CSA C/US approval
P1 = T
p
: 0 °C (+32 °F) | T
a
: +76 °C (+169 °F)
P2 = T
p
: +76 °C (+169 °F) | T
a
: +76 °C (+169 °F)
P3 = T
p
: +200 °C (+392 °F) | T
a
: +27 °C (+81 °F)
P4 = T
p
: +200 °C (+392 °F) | T
a
: 0 °C (+32 °F)
P5 = T
p
: 0 °C (+32 °F) | T
a
: 0 °C (+32 °F)