Proline Prowirl 73 Description of device functions
Endress+Hauser 139
BURST MODE CMD Prerequisite
The BURST MODE CMD function is only available if OFF was selected in the BURST
MODE function (ä 138).
Description
For selecting process values that are cyclically transmitted to the HART master in the
burst mode.
Options
CMD 1
Read primary measured variable (e.g. volume flow).
CMD 2
Read current and percentage of the measuring range
CMD 3
Read current and four (previously defined) measured variables.
(see HART Command No. 51, ä 45).
Factory setting
CMD 1
MANUFACTURER ID Description
The manufacturer number in decimal numerical format appears on the display.
Display:
17 = (11 hex) for Endress+Hauser
DEVICE ID Description
The device number in hexadecimal numerical format appears on the display.
Display:
57 = (87 dec) for Prowirl 73
Function description, COMMUNICATION group