Technical data Waterpilot FMX21
122 Endress+Hauser
16 Technical data
16.1 Input
16.1.1 Measured variable
FMX21 + Pt100 (optional)
• Hydrostatic pressure of a liquid
• Pt100: Temperature
TMT182 temperature head transmitter (optional)
Temperature
16.1.2 Measuring range
• Customer-specific measuring ranges or calibration that has been preset in the factory
• Temperature measurement of –10 to +70 °C (+14 to +158 °F) with Pt100 (optional)
Relative pressure
Sensor measuring range Lowest calibratable span
1)
Vacuum resistance Option
2)
[bar (psi)] [bar (psi)] [bar
abs
(psi
abs
)]
0.1 (1.5) 0.01 (0.15) 0.3 (4.5) 1C
0.2 (3.0) 0.02 (0.3) 0.3 (4.5) 1D
0.4 (6.0) 0.04 (1.0) 0 1F
0.6 (9.0) 0.06 (1.0) 0 1G
1.0 (15.0) 0.1 (1.5) 0 1H
2.0 (30.0) 0.2 (3.0) 0 1K
4.0 (60.0) 0.4 (6.0) 0 1M
10.0 (150)
3)
1.0 (15) 0 1P
20.0 (300)
3)
2.0 (30) 0 1Q
1) Recommended maximum turn down: 100:1. Highest turn down that can be preset at the factory: 20:1,
higher available on request.
2) Product Configurator order code for "Sensor range"
3) These measuring ranges are not available for the special version with plastic insulation, external diameter
of 29 mm (1.14 in).
Absolute pressure
Sensor measuring range Lowest calibratable span
1)
Vacuum resistance Option
2)
[bar (psi)] [bar (psi)] [bar
abs
(psi
abs
)]
2.0 (30.0) 0.2 (3.0) 0 2K
4.0 (60.0) 0.4 (6.0) 0 2M