Integrating device via HART
®
protocol
Waterpilot FMX21
36 Endress+Hauser
8
Integrating device via HART
®
protocol
Version data for the device
Firmware version 01.00.zz • On the title page of the Operating instructions
• On nameplate
• Firmware Version parameter
Diagnosis→ Instrument info → Firmware version
Manufacturer ID 17 (0x11) Manufacturer ID. parameter
Diagnosis → Instrument info→ Manufacturer ID
Device type code 36 (0x24) Device type parameter
Diagnosis → Instrument info → Device type
HART protocol revision 6.0 ---
Device revision 1 • On transmitter nameplate
• Device revision parameter
Diagnosis→ Instrument info → Device revision
The suitable device description file (DD) for the individual operating tools is listed in the
table below, along with information on where the file can be acquired.
Operating tools
Operating tool Reference sources for device descriptions (DD and DTM)
FieldCare • www.endress.com → Downloads area
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
www.endress.com → Downloads area
SIMATIC PDM
(Siemens)
www.endress.com → Downloads area
Field Communicator 375, 475
(Emerson Process Management)
Use update function of handheld terminal
8.1 HART process variables and measured values
The following numbers are assigned to the process variables in the factory:
Process variable Meas. Level
Linear Table active
First process variable
(Primary variable)
0
(Pressure measured)
8
(Level before
linearization)
9
(Tank content)
Second process variable
(Secondary variable)
2
(Corrected press.)
0
(Pressure measured)
8
(Level before
linearization)