Description of device parameters Waterpilot FMX21
98 Endress+Hauser
14.11 Expert → Output → Current output
Output current
Write permission Operators/Service engineers/Expert
Description Displays the current current value.
Alarm behav. P
Write permission Operators/Service engineers/Expert
Description Behavior of current output if sensor module limits are are exceeded or not reached.
Options • Warning
The device continues to measure. An error message is displayed.
• Alarm
The output signal assumes a value that can be specified by the "Output fail mode"
function.
Factory setting Warning
Output fail mode
Write permission Operators/Service engineers/Expert
Description Select Output fail mode. In the event of an alarm, the current assumes the current value
specified with this parameter.
Options • Max: can be set from 21 to 23 mA, see also "High alarm curr."
• Hold: last measured value is held.
• Min: 3.6 mA
Factory setting Max (22 mA)
High alarm curr.
Write permission Operators/Service engineers/Expert
Description Enter the current value for maximum alarm current. See also "Output fail mode".
Input range 21 to 23 mA