Waterpilot FMX21 Commissioning
Endress+Hauser 49
Description
3 Select the "In height" level mode via the "Level
selection" parameter.
Menu path: Setup → Extended setup → Level →
Level selection.
1 See table, steps 10 and 11.
2 See table, steps 13 and 14.
3 See table, step 12
4 If density correction is required, assign the
temperature probe in the "Auto dens. corr."
parameter.
Menu path: Setup → Extended setup → Level →
Level selection.
4 Select a volume unit via the "Unit before lin."
parameter, here "l" (liter) for example.
Menu path: Setup → Extended setup → Level→
Unit before lin.
A density correction is only possible for water.
A temperature-density curve that is saved in
the device is used. For this reason, the "Adjust
density" (step 12) and "Process density" (step
15) parameters are not used here.
5 Select a volume unit via the "Output unit"
parameter, here here "l" (liter) for example.
Menu path: Setup → Extended setup → Level →
Output unit
6 Select a level unit via the "Height unit"
parameter, "m" for example.
Menu path: Setup → Extended setup → Level →
Height unit