Waterpilot FMX21 Commissioning
Endress+Hauser 55
FXN520
OPEN
CLOSE
90°
90°
Warning:
Avoid electrostatic charge in explosive atmosphere.
See instructions
Terminal Box for FMX21
1 2
4
3
5
A0018821
1 Fieldgate FXA520
2 Multidrop connector FXN520
3 Terminal box (can be ordered as an accessory)
4 Cerabar M absolute pressure (atmospheric pressure)
5 Waterpilot absolute pressure (level)
Adjustment of the level sensor (Waterpilot)
1 Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in the "Setup"
operating menu and readjusted if necessary.
2 Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3 The sensor is unpressurized, perform a position adjustment →  40
4 Switch on burst mode via the "Burst mode" parameter.
Menu path: Expert → Communication → HART config
5 Set the output current to "Fixed" 4.0 mA via the "Current Mode" parameter.
Menu path: Expert → Communication → HART config
6 Configure an address ≠0 using the "Bus address" parameter, e.g. bus address = 1.
(HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling" setting; HART 6.0 master:
Range 0 to 63)
Menu path: Expert → Communication → HART config