1. Installation
1−5
Festo P.BE−CPX−FB13−EN en 0811c
Note
Use protective caps or blanking plugs to seal unused
connections. You will then comply with protection class
IP65/IP67 (see section 1.3.4).
Dismantling and fitting
The field bus node is fitted in a manifold base of the
CPXterminal (see Fig.1/2).
Dismantling Dismantle the field bus node as follows:
1. Loosen the 4 screws in the field bus node with a TORX
screwdriver size T10.
2. Pull the field bus node carefully and without tilting away
from the contact rails of the manifold
base.
1 Field bus node
CPX−FB13
2 Manifold base
3 Contact rails
4 TORX T10 screws
3
4
1
2
Fig.1/2: Dismantling/fitting the field bus node