Calculating with graphs
Proceed as follows:
1. Calculate the maximum current consumption
of the outputs/valves (I
2
).
2. Calculate the lowest voltage to be expected
on the power unit during operation (V
Omin
).
Take into consideration:
the inluence of load variation of the power
unit
the fluctuations in the primary mains voltage.
3. Read the permitted length of cable in the
table for the relevant cross section.
Example for 1.5 mm
2
:
V
Omin
= 22.8 V, I
2
= 2 A; L
max
= 25 m