Accutronix MX Maintenance & Spare Parts Manual 130-12000 Revision B • November 2002
5-6
Flow Control Division
Limitorque Actuation Systems
Electronic Assemblies
STEP 4
Disconnect wire harness plugs P1 and P2 from the main power board.
STEP 5
Using a 3 mm hex key, loosen the three M4 mounting plate screws
(#8-7) located at the back of the controls compartment. Slightly rotate
the complete control module assembly in a counterclockwise (CCW)
direction, until the keyhole slots in the baseplate (#8-1) allow the
heads of the screws to pass through.
STEP 6
Disconnect the AMP® power connector from the fuse section of the
main power board.
4
6
5
P1
AMP Plug
8-7
P2